STP Not Achieving Required BOD/COD Levels? Here’s What to Check

A Sewage Treatment Plant (STP) may be running continuously, yet the treated water at the outlet may fail to achieve the required Biological Oxygen Demand (BOD) and Chemical Oxygen Demand (COD) levels. This can indicate problems with biological treatment, aeration, sludge management, hydraulic loading, or the overall treatment process. If the issue continues, it may affect environmental compliance, treated water reuse, operating costs and plant performance. For residential complexes, commercial buildings, industrial facilities, hospitals and infrastructure projects, maintaining consistent STP performance is essential. So, what should you check when your STP is not achieving the required BOD/COD levels?
Let’s explore the common causes and practical troubleshooting measures.
What Are BOD and COD in Sewage Treatment?
Before troubleshooting an STP, it is important to understand what these parameters indicate.
1. Biological Oxygen Demand (BOD)
BOD measures the oxygen consumed by microorganisms while breaking down biodegradable organic matter in wastewater under specified test conditions. A high BOD concentration in treated water may indicate that biodegradable organic pollutants are not being adequately removed during treatment.
2. Chemical Oxygen Demand (COD)
COD measures the oxygen equivalent required to chemically oxidize substances in wastewater under a specified test method. High COD in the treated outlet may indicate the presence of residual organic pollutants, including compounds that may be difficult to biodegrade.
Why should you monitor both?
BOD and COD provide complementary information about wastewater quality and treatment performance. Comparing influent and outlet results can help determine whether the treatment process is effectively reducing the organic pollution load. However, high BOD or COD alone does not identify the exact cause. A systematic assessment of the entire STP is necessary.
8 Common Reasons Why an STP Fails to Meet BOD/COD Limits
1. Inadequate Aeration in the Biological Treatment System
Aeration is essential in aerobic treatment processes because it supplies oxygen to microorganisms responsible for breaking down biodegradable pollutants. If oxygen transfer is insufficient, biological treatment efficiency may decline, resulting in elevated outlet BOD and potentially higher COD.
What to check:
- Dissolved oxygen (DO) levels in the aeration tank.
- Blower performance and operating pressure.
- Blocked, damaged, or clogged diffusers.
- Air distribution throughout the tank.
- Mixing conditions and equipment maintenance.
Recommended action: Assess oxygen demand, airflow distribution, and aeration equipment performance. Optimize aeration based on the treatment system’s operating requirements rather than simply increasing blower operation.
2. Poor Biological Sludge Health
Biological treatment depends on a healthy and adequately maintained microbial population. Sudden changes in pH, toxic substances, temperature, organic loading, or nutrient availability can affect microbial activity and reduce treatment efficiency.
Warning signs may include:
- Increasing outlet BOD.
- Unusual foam or changes in sludge appearance.
- Poor sludge settling.
- Fluctuating dissolved oxygen demand.
- Changes in mixed liquor suspended solids (MLSS).
Recommended action: Review MLSS, mixed liquor volatile suspended solids (MLVSS), sludge age, pH, nutrient availability and other relevant biological operating parameters. Investigate any sudden changes in incoming wastewater.
3. Excessive Hydraulic or Organic Loading
An STP is designed to treat a specified wastewater flow and pollution load. If the incoming sewage volume or organic load exceeds the plant’s design capacity, treatment efficiency may decline.
This can happen when:
- Occupancy increases in a residential or commercial facility.
- New production or utility areas add wastewater.
- Peak flows exceed the system’s hydraulic capacity.
- High-strength wastewater enters the STP unexpectedly.
Recommended action: Compare current wastewater flow and organic loading with the original design criteria. Review equalization, hydraulic retention time and the capacity of individual treatment units.
If overloading is confirmed, process optimization or capacity enhancement may be required.
4. Incorrect Sludge Age or MLSS Management
Sludge management plays a significant role in biological treatment performance. Excessive sludge wasting can reduce the microbial population available for treatment. Conversely, poor sludge wasting or excessive solids accumulation may create operational problems, depending on the treatment configuration.
What to check:
- MLSS and MLVSS trends.
- Sludge retention time (SRT).
- Sludge wasting and return sludge rates, where applicable.
- Sludge settling characteristics.
- Sludge blanket levels and solids carryover.
Recommended action: Adjust sludge management based on the specific STP process, design parameters and biological performance data. Avoid changing sludge wasting rates without evaluating the overall system.
5. Poor Performance of the Secondary Clarifier
Even when biological treatment is effective, poor solids separation can allow suspended solids and associated organic matter to escape with the treated effluent. This can contribute to elevated BOD and COD results.
Possible causes include:
- Poor sludge settling.
- Excessive hydraulic loading.
- Sludge blanket accumulation.
- Hydraulic short-circuiting.
- Inadequate sludge withdrawal.
- Floating sludge or solids carryover.
Recommended action: Inspect clarifier operation, sludge settling characteristics, sludge blanket levels and outlet water clarity. Check whether high outlet readings coincide with elevated total suspended solids (TSS).
6. Sudden Changes in Influent Sewage Quality
Incoming sewage characteristics may vary because of changes in occupancy, cleaning activities, commercial operations, or the introduction of unusual wastewater streams. A sudden increase in organic loading or the presence of inhibitory substances can disturb the biological treatment process.
What to check:
- Influent BOD and COD trends.
- Daily wastewater flow variations.
- pH and temperature fluctuations.
- Unusual cleaning chemicals or discharges.
- Changes in occupancy or operating schedules.
Recommended action: Characterize the incoming wastewater and identify the source of significant variations. Where appropriate, use equalization and source control to reduce sudden load fluctuations.
7. Inadequate Nutrient Balance or Unstable pH
Microorganisms need suitable environmental conditions and an adequate supply of nutrients to perform effectively. An unsuitable pH or nutrient imbalance may restrict biological activity and reduce organic pollutant removal.
What to check:
- pH in the biological treatment stage.
- Nutrient availability relative to the wastewater characteristics.
- Changes in incoming wastewater composition.
- Evidence of biological process instability.
Recommended action: Correct nutrient or pH imbalances based on wastewater analysis and process requirements. Avoid adding nutrients or chemicals without confirming that a deficiency or imbalance exists.
8. Ineffective Tertiary Treatment or Treatment-Process Limitations
Some STPs require additional treatment stages to achieve the specified outlet quality, particularly when treated water is intended for reuse or when discharge requirements are stringent. Depending on the design, these stages may include filtration, membrane treatment, or other polishing processes. If the existing treatment train is unsuitable for the incoming wastewater or the required outlet quality, BOD and COD performance may remain inconsistent.
Recommended action: Evaluate the complete treatment sequence, including biological treatment, clarification, filtration and any advanced treatment units. Select modifications according to the actual wastewater characteristics and applicable discharge or reuse requirements.
Practical STP Troubleshooting Checklist
If your STP is consistently failing to meet BOD/COD limits, follow a structured investigation before making major operational changes.
Step 1: Verify the Laboratory Results
Review the sampling location, sampling procedure, preservation, testing method and laboratory results. Repeat sampling when necessary to confirm the problem.
Step 2: Compare Influent and Outlet Results
Evaluate BOD, COD, TSS, pH and flow data together. This helps establish whether the problem originates in biological treatment, solids separation, or another treatment stage.
Step 3: Review Operating Conditions
Check dissolved oxygen, MLSS/MLVSS, sludge age, hydraulic loading and other process-specific parameters.
Step 4: Inspect Mechanical Equipment
Assess blowers, diffusers, pumps, mixers, sludge withdrawal systems and clarifier operation.
Step 5: Identify the Root Cause
Use operating data and wastewater analysis to determine whether the issue is related to overloading, biological instability, inadequate aeration, solids carryover, or treatment-process limitations.
Step 6: Implement Corrective Measures and Monitor Results
Make controlled adjustments based on the findings. Track the relevant parameters over time to verify whether the corrective measures are effective.
How Can You Improve STP Performance?
Improving STP performance requires a combination of proper design, effective operation, preventive maintenance and regular monitoring. Depending on the identified problem, improvement measures may include:
- Optimizing aeration and biological treatment conditions.
- Improving sludge management and clarifier performance.
- Managing flow variations through appropriate equalization.
- Controlling unsuitable or unusually concentrated wastewater streams.
- Optimizing chemical dosing where chemical treatment is part of the process.
- Improving preventive maintenance and operational monitoring.
- Assessing whether additional treatment or system modification is required.
Technologies such as Activated Sludge Process (ASP), Moving Bed Biofilm Reactor (MBBR), Sequencing Batch Reactor (SBR) Membrane Bioreactor (MBR) and Decentralized Multi-Stage Reactor (UDMSR) may be suitable for different applications. The correct choice depends on the influent characteristics, design capacity, available space, treated-water requirements and operating conditions.
No single technology or operating adjustment is suitable for every STP.
What BOD and COD Limits Should Your STP Achieve?
The required treated-water quality depends on the applicable environmental standards, regulatory directions, consent conditions, discharge destination and intended reuse. For example, certain Indian standards for specified categories of new STPs have prescribed BOD limits of 10 mg/L and COD limits of 50 mg/L. These values should not be assumed to apply to every existing plant or every discharge scenario. Before deciding on corrective measures, verify the requirements applicable to your specific facility with the relevant State Pollution Control Board or Pollution Control Committee and review the plant’s consent conditions. Meeting the applicable requirements should be the objective of the treatment system’s design and operation.
How CIEMS Can Help Improve Your STP Performance
CIEMS provides wastewater treatment solutions, including STP and ETP design, installation, operation and maintenance support and treatment-process optimization. Its solutions include technologies such as ASP, MBBR, SBR, MBR and UDMSR selected according to project requirements. If your STP is not achieving the required BOD/COD levels, a technical assessment can help identify the underlying causes and determine appropriate corrective measures.
The assessment may include:
- Reviewing influent and outlet wastewater quality.
- Evaluating treatment capacity and process configuration.
- Assessing aeration, biological treatment and sludge management.
- Inspecting mechanical equipment and treatment stages.
- Recommending process optimization or system modifications.
- Reviewing the applicable environmental compliance requirements.
The objective is to improve treatment reliability, support compliance and reduce avoidable operational problems.
Need help troubleshooting your STP?
Contact CIEMS to discuss your wastewater treatment challenges and explore a solution suited to your facility.
Conclusion
An STP that fails to achieve the required BOD/COD levels may be experiencing problems with aeration, biological sludge health, hydraulic loading, sludge management, clarifier performance, influent variations, or treatment-process limitations. The most effective response is to verify the results, assess the complete treatment system, identify the root cause and implement corrective measures supported by operational data.
With appropriate monitoring, preventive maintenance and process optimization, facilities can work towards more consistent wastewater treatment performance and their applicable environmental requirements.